»Ê¼Ò»ªÈË

XClose

Estates

Home
Menu

Fire Extinguishers

Experience has shown that most fires which have been discovered in their early stages can be successfully tackled and extinguished by the use of portable fire extinguishers. Portable fire extinguishers are valuable in the early stages of fire when their portability and immediate availability for use by one person enables a prompt attack to be made.

Fire Extinguisher policy and safety guidanceÌý


  1. In the event of aÌýfire, occupants should move away from the immediate location of the fire to a place of relative safetyÌý(i.e. corridor, landing or stair enclosure).
  2. Occupants will generally find aÌý'fire point'Ìýcontaining fire-fighting equipment and a red ‘manual call point’ for raising alarm and to warn other occupants.
  3. Fire Extinguishers are only to be purchased and maintained by the UCL Fire Team. Departments are not permitted to purchase Fire Extinguishers, all requests must come through the UCL Fire Team for approval.Ìý
  4. On a fire being observed or discovered:
  • Firstly area occupants should leave area, operate the nearest break glass fire alarm call point (MCP) and where practicable, dial ‘222’ or as appropriate and raise the alarm.
  • Secondly make a judgement on whether or not,Ìýit is safe and practicable to return to tackle the fireÌýwith a suitable extinguisher?
  • Only go back and attack the fire with an appropriate fire extinguisherÌýif it safe and you are confident to do so -Ìýdo not place yourself or others at riskÌý- if in doubtÌýget out.
  • Thirdly ifÌýin doubt, leave by building by the nearest fire exit, ensuring that the alarm is raised.

Ìý

Fire Extinguisher Maintenance / ChecklistÌý


Extinguishers are only tested and inspected annually by a Service Engineer arranged by the UCL Fire Team only.Ìý Therefore, any damage or problems may leave the extinguisher unserviceable for some considerable time before being rectified - this may then become a potential life safety issue.

Departments should undertake a visual inspection of Fire Extinguishers to ensure that they appear serviceable, available for use and unobstructed using (see TN_026).Ìý Reporting promptly any suspected defects or malicious discharges to the UCL Fire Safety Team (fire@ucl.ac.uk).Ìý

Every department at »Ê¼Ò»ªÈË must carry out a monthly check on Fire Extinguishers. Below is a quick guide to help you select the right extinguisher and a handy checklist for you to download.Ìý

Download the department guide and record sheet for carrying out your monthly check on fire extinguishers.Ìý

Ìý

Fire extinguisher trainingÌý


We do not encourage you to use a fire extinguisher unless you have been trained and are competent to do so.Ìý

> fire extinguisher training

    Ìý

    Quick guide to selecting the right extinguisher


    Detailed technical notes are available from the UCL Fire Safety Sharepoint site. If you have any problems accessing the SharePoint site, please email fire@ucl.ac.uk

    • (TN024)
    • (TN025)
    Water Mist(TN027a)
    WaterÌý(TN027)
    Foam Multi-purposeÌý(TN029)
    Carbon DioxideÌý(TN030)
    Fire BlanketÌý(TN035)
    Dry PowderÌý(TN031)
    Dry Powder-L2(TN036)
    Dry Powder-M28(TN033)
    Dry Powder-Monnex(TN032)
    Foam PolarÌý(TN029a)
    Foam Wet Chemical(TN034)
    Fume Cupboard Suppression Systems

    Ìý(TN037)Ìý
    Ìý(TN038a)

    Hose ReelÌý(TN028)

    Ìý

    Fire hydrants


    Hydrant marker post and indicator plate are in position and correct for main size, distance and hydrant identification number is marked on post.

    The top number indicates the size in mm of the water main feeding the fire hydrant (100 mm)

    The lower number indicates in metres the distance from hydrant pate the hydrants cover is away (i.e. 20 m) The hydrant lid/frame shall be identified by being painted to conform to Colour Reference No: 309 (Canary Yellow), BS 381C.

    Plates should be a not less than 180 mm wide by 205 mm high

    Ìý

    LegionellaÌý


    • Ìý(TN073)

    Ìý

    Related fire safety information


    Ìý